XCKP2121P16
Limit switch, Limit switches XC Standard, XCKP, thermoplastic plastic roller lever plung. Hor, 1NC+1 NO, snap, M16
This XCKP compact format (CENELEC EN 50047) limit switch has a steel roller lever plunger with horizontal actuation and a plastic body. This limit switch has a double insulated thermoplastic body, a modular design allowing easier maintenance and a compact CENELEC EN50047 format. It is IP66 and IK04 impact resistant, making it ideal for heavy duty use in harsh conditions. It is fixed on the machine by its body, and has a typical 5 million cycles electrical durability in DC-13 utilization category. It complies with CCC, EN/IEC 60947.-5-1, CSA C22.2 No.14, EN/IEC 60204-1, UL 508 standards. Compatible with the well distributed range of common XCK heads, allowing quick replacement in case of damage. Variable composition design allows late modifications on the switch, for example change of connection type or head.
Main | |
Range of product | Telemecanique Limit switches XC Standard |
---|---|
Series name | Standard format |
Product or component type | Limit switch |
device short name | XCKP |
Sensor design | Compact form E conforming to CENELEC EN 50047 |
body type | Fixed |
Head type | Plunger head |
Material | Plastic |
body material | Plastic |
Head material | Zamak |
fixing mode | By the body |
Movement of operating head | Linear |
Type of operator | Spring return roller lever plunger thermoplastic |
Type of approach | Lateral approach, 1 direction |
Number of poles | 2 |
contacts type and composition | 1 NC + 1 NO |
contact operation | Snap action |
Complementary | |
Switch actuation | By 30° cam |
---|---|
Electrical connection | Screw-clamp terminals, clamping capacity: 1 x 0.34...2 x 1.5 mm² |
Cable entry | 1 entry tapped for M16 x 1.5 cable gland, cable outer diameter: 4…8 mm |
Contacts insulation form | Zb |
Positive opening | With |
Positive opening minimum force | 18 N |
Minimum force for tripping | 6 N |
Maximum actuation speed | 1 m/s |
Repeat accuracy | 0.1 mm on the tripping points with 1 million operating cycles |
Contact code designation | A300, AC-15 (Ue = 240 V), Ie = 3 A, Ithe = 10 A conforming to EN/IEC 60947-5-1 appendix A Q300, DC-13 (Ue = 250 V), Ie = 0.27 A conforming to EN/IEC 60947-5-1 appendix A |
[Ui] rated insulation voltage | 300 V conforming to UL 508 500 V (pollution degree 3) conforming to IEC 60947-1 300 V conforming to CSA C22.2 No 14 |
Maximum resistance across terminals | 25 MOhm conforming to IEC 60255-7 category 3 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60664 6 kV conforming to IEC 60947-1 |
Short-circuit protection | 10 A cartridge fuse, type gG |
Electrical durability | 5000000 cycles, DC-13, 120 V, 4 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 5000000 cycles, DC-13, 24 V, 10 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 5000000 cycles, DC-13, 48 V, 7 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C |
Mechanical durability | 15000000 cycles |
Width | 31 mm |
Height | 65 mm |
Depth | 30 mm |
Net weight | 0.105 kg |
Terminals description ISO n°1 | (21-22)NC (13-14)NO |