ZB4BZ103
ZB4BZ103 - SCHNEIDER
Harmony XB4, Single contact block with body fixing collar, metal, screw clamp terminal, 2NO
In Stock
Description
This Harmony XB4, single contact block is pre-assembled on a body/collar fixing unit. It has 2 x NO contacts and a chromium-plated metal bezel. It is compatible with Harmony XB4 This body fixing collar is pre-mounted with a contact block. Simply adding a head to this assembly will provide you with a complete ready-to-use push button. It protects operators from unexpected contact with live circuits thanks to its IP20 protection index. 1 million cycle high endurance provides less maintenance and damage in your installation. Its wide range of operating temperatures from -40°C to 70°C allows versatility in usage of product.
Specifications
Range of product Harmony XB4 product or component type Complete body/contact assembly Device short name ZB4 Fixing collar material Zamak Sale per indivisible quantity 1 Head type Standard Contacts type and composition 2 NO Contact operation Slow-break Contact block type Single device composition Body
Fixing collarConnections - terminals Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to IEC 60947-1
Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to IEC 60947-1Complementary
CAD overall width 30 mm CAD overall height 47 mm CAD overall depth 37 mm Terminals description ISO n°1 (13-14)NO net weight 0.062 kg Contacts usage Standard contacts Positive opening Without Operating travel 2.6 mm (NO changing electrical state)
4.3 mm (total travel)Operating torque 0.05 N.m NO changing electrical state Mechanical durability 5000000 cycles Tightening torque 0.8…1.2 N.m conforming to IEC 60947-1 Shape of screw head Cross compatible with Philips no 1 screwdriver
Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriverContacts material Silver alloy (Ag/Ni) Short-circuit protection 10 A cartridge fuse type gG conforming to IEC 60947-5-1 [Ith] conventional free air thermal current 10 A conforming to IEC 60947-5-1 [Ui] rated insulation voltage 600 V (pollution degree 3) conforming to IEC 60947-1 [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-1 [Ie] rated operational current 3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1Electrical durability 10000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
10000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
10000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
10000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
10000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix CElectrical reliability Λ < 10exp(-6) at 5 V, 1 mA in clean environment conforming to IEC 60947-5-4
Λ < 10exp(-8) at 17 V, 5 mA in clean environment conforming to IEC 60947-5-4device presentation Basic sub-assemblies Environmental
protective treatment TH ambient air temperature for storage -40…70 °C Ambient air temperature for operation -40…70 °C IP degree of protection IP20 conforming to IEC 60529 Standards JIS C8201-5-1
IEC 60947-1
IEC 60947-5-4
CSA C22.2 No 14
IEC 60947-5-1
IEC 60947-5-5
UL 508
JIS C8201-1Product certifications BV
CSA
UL
DNV
LROS (Lloyds register of shipping)
GLVibration resistance 5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6 Shock resistance 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27