ZBE101
ZBE101 - SCHNEIDER
Single contact block, silver alloy, screw clamp terminal, 1 NO
In Stock
Description
This Harmony ZB, single contact block uses screw clamp terminals. This contact block allows fast and easy replacement and configuration of your push buttons and selector switches. It is easily installed and replaced on XB4 or XB5 complete push-button units and selector switches via a clip assembly and connects to control circuits with simple screw-clamp connections. It protects operators from unexpected contact with live circuits thanks to its IP20 protection index. 1 million cycle high endurance under 6A load allows less maintenance and damage in your installation. It has clear color scheme. Vibration resistant screw clamp connection terminals ensure high vibration resistance making product suitable installation on high impact machine.
Specifications
Range of product Harmony XB5
Harmony XB4product or component type Contact block Device short name ZBE Sale per indivisible quantity 5 IP degree of protection IP20 conforming to IEC 60529 Contact operation Slow-break Contact block type Single Contacts usage Standard contacts Connections - terminals Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to IEC 60947-1
Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to IEC 60947-1Complementary
net weight 0.011 kg Contacts type and composition 1 NO Positive opening Without Operating travel 2.6 mm (NO changing electrical state)
4.3 mm (total travel)Operating force 2.3 N NO changing electrical state Mechanical durability 10000000 cycles Tightening torque 0.8…1.2 N.m conforming to IEC 60947-1 Shape of screw head Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriverContacts material Silver alloy (Ag/Ni) Short-circuit protection 10 A cartridge fuse type gG conforming to IEC 60947-5-1 [Ith] conventional free air thermal current 10 A conforming to IEC 60947-5-1 [Ui] rated insulation voltage 600 V (pollution degree 3) conforming to IEC 60947-1 [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-1 [Ie] rated operational current 3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1Electrical durability 1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix CMounting of block Front mounting Electrical composition code C1 (quantity <= 9)
C2 (quantity <= 7)
C3 (quantity <= 6)
C4 (quantity <= 4)
C5 (quantity <= 5)
C6 (quantity <= 3)
C7 (quantity <= 4)
C8 (quantity <= 2)
C9 (quantity <= 3)
C12 (quantity <= 6)
M1 (quantity <= 6)
M2 (quantity <= 4)
M3 (quantity <= 4)
M5 (quantity <= 2)
M6 (quantity <= 2)
M7 (quantity <= 6)
M8 (quantity <= 4)
M9 (quantity <= 2)
SF1 (quantity <= 3)
SF2 (quantity <= 2)
MF1 (quantity <= 2)
MF2 (quantity <= 2)
C10 (quantity <= 2)
M4 (quantity <= 2)
C13 (quantity <= 1)device presentation Basic element Environmental
protective treatment TH ambient air temperature for storage -40…70 °C Ambient air temperature for operation -40…70 °C Standards CSA C22.2 No 14
IEC 60947-5-1
UL 508
IEC 60947-1
JIS C8201-5-1
IEC 60947-5-4
JIS C8201-1Product certifications CCC
UL
DNV
GL
GOST
LROS (Lloyds register of shipping)
BV
CSAVibration resistance 5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6 Shock resistance 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27